Description

INSTRUMENTATION CABLES, Acc. to BS 5308 PART 1 TYPE 1 SİNGLE & MULTİ-TRIPLE, PE INSULATED, COLLECTİVE SCREENED, PVC SHEATHED Marking BIRTAS KABLO RE-2Y(St)Y-fl 2 x 3 x 0.50mm2 1603 11 002 BS 5308 Part no GOST-R CE....mt Applications These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... . Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. These cables are not recommended for direct burial. They are for indoor and oudoor installation, in dry and wet locations; on racks, trays, in conduits. Cable Design Conductor Plain annealed copper wire, BS 6360 ,0,50 mm2 and 1,0 mm2 solid, 0,50 mm2 and 0,75 mm2 flexible or 1,5 mm2 stranded Insulation PE compound, BS 6234 Type03 Core identification...

Product features

Standard Designed acc. to BS 5308 Part 1 Type 1
Insulation thickness 0,50mm 1,0mm2 : 0,60mm 0,50mm2 : 0,60mm 0,75mm2 : 0,60mm 1,50mm2 : 0,60mm
Conductor class, BS 6360 Class 1 1,0mm2 : Class 1 0,50mm2 : Class 5 0,75mm2 : Class 5 1,5mm2 : Class 2
Conductor resistance 36,8 Ω/km 1,0mm2 : 18,4 Ω/km 0,50mm2 : 39,7 Ω/km 0,75mm2 : 26,5 Ω/km 1,5mm2 : 12,3 Ω/km
Insulation resistance Min. 5000 MΩ.km
Mutual Capacitance max. 115 pF/m (≤2 pairs),max. 75 pF/m (all other pairs) 0,75 mm2 : max. 115 pF/m (≤2 pairs),max. 75
Capacitance unbalance max. 250 pF/250 m
L / R (ratio) (max.) 25 µH/Ω 0,75mm2 : 25 µH/Ω 1,0mm2 : 25 µH/Ω1,5mm2 : 40 µH/Ω
Rated voltage 300/500V
Test voltage 1000 V Urms core-screen : 1000 V
Temperature range - 40 oC ~ + 70 oC ınstallation : - 5 oC ~ + 50 oC
Min. bending radius 6 x D
Flame retardance test IEC 60332-1 & BS EN 60332-1