Description

INSTRUMENTATION CABLES, Acc. to BS 5308 PART 1 TYPE 2 MULTİ-TRIPLE, PE INSULATED, INDIVIDUAL & COLLECTİVE SCREENED, ARMOURED, PVC SHEATHED Marking BIRTAS KABLO RE-2Y(St)2Y SWAY-fl TİMF 10 x 3 x 0.50mm2 1608 05 010 BS 5308 Part no GOST-R CE....mt Applications These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... . Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. The armour above the inner sheath protects the cable from mechanical shocks. These cables are recommended for direct burial. They are for indoor and oudoor installation, in dry and wet locations; on racks, trays, in conduits. Cable Design Conductor Plain annealed copper wire, BS 6360 ,0,50 mm2 and 1,0 mm2 solid, 0,50 mm2...

Product features

Standard Designed acc. to BS 5308 Part 1 Type 2
Insulation thickness 0,50mm 1,0mm2 : 0,60mm 0,50mm2 : 0,60mm 0,75mm2 : 0,60mm 1,50mm2 : 0,60mm
Conductor class, BS 6360 Class 1 1,0mm2 : Class 1 0,50mm2 : Class 5 0,75mm2 : Class 5 1,5mm2 : Class 2
Conductor resistance 36,8 Ω/km 1,0mm2 : 18,4 Ω/km 0,50mm2 : 39,7 Ω/km 0,75mm2 : 26,5 Ω/km 1,5mm2 : 12,3 Ω/km
Insulation resistance Min. 5000 MΩ.km
Mutual Capacitance max. 115 pF/m 0,75 mm2 : max. 115 pF/m 1,0 mm2 : max. 115 pF/m 1,5 mm2 : max. 120 pF/m
Capacitance unbalance max. 250 pF/250 m
L / R (ratio) (max.) 25 µH/Ω 0,75mm2 : 25 µH/Ω 1,0mm2 : 25 µH/Ω1,5mm2 : 40 µH/Ω
Rated voltage 300/500V
Test voltage 1000 V Urms core-screen : 1000 V
Temperature range - 40 oC ~ + 70 oC ınstallation : - 5 oC ~ + 50 oC
Min. bending radius 8 x D
Flame retardance test IEC 60332-1 & BS EN 60332-1