Description

PVC INSULATED, SCREENED FIRE ALARM INSTALLATION CABLES Marking BIRTAS KABLO J-Y(St)CY lg FİRE ALARM 3 x 2 x 1.38mm 1213 08 003 Part no GOST-R CE ……mt Applications These cables are used for fire alarm cables as an fixed indoor installations. Double screened provides more protection against electromagnetic interferences. Additionally these cables are suitable for applications at small bending radius. Cable Design Conductor Plain copper conductor, solid NOTE: Upon request all conductors can be with tinned copper Insulation PVC compound , YI1; VDE 0207-4 Core identification VDE 0815 Pair Two conductors twisted to a pair 2 pairs twisted as star-quad Lay-up Pairs laid up in layers of optimum pitch Separator Polyester tape Screen Tinned Cu drain wire under the AL-PES tape Drain wire; phi : 0,40 mm ≤ 10 pairs phi : 0,60 mm > 10 pairs Braid of tinned Cu wires, 65% coverage Screen Braid of tinned Cu wires, 65% coverage Outer sheath PVC compound, YM1; VDE 0207-5 Sheath colour...

Product features

Standard VDE 0815
Conductor resistance (loop) 65 Ω/km 0,80mm : 36 Ω/km 1,0mm : 43,8 Ω/km 1,38mm : 23,0 Ω/km
Insulation resistance Min. 100 MΩ.km
Mutual Capacitance Max. 100 nF/km This value may be exceeded by 20% by cables with up to 4 pairs
Capacitance unbalance Max. 300 pF / 100 mt 20% of the values, at least one value up to 500 pF permitted.
Test voltage 800 V
Temperature range - 30 oC ~ + 70 oC
Min. bending radius 10xD
Flame retardance test IEC 60332-1 & EN 50265-2-1
Rated voltage, peak Max. 300 V up to 600V permissible for short periods (6 s/min)