Freon Refrigerant R-141b 13.6 kg Ready To Ship

R141B Refrigerant
Web icon

Description

Cleaning the system with freon R141b (flushing liquid), similar to R11, can Be carried out by circulating through a pump with the connection of standard equipment (valves, inspection windows, fittings and filters) or using liquid nitrogen (pressure 7-8 bar). Vessels with R141b freon, equipped with connecting valves, can oe pressurized oy the consumer himself, out not more than 2/3 of the service pressure of the cylinders and with a maximum limit of 10 bar. For this, use pressure gauges connected to nitrogen cylinders. To increase cleaning power, it is recommended to use R141b freon separately for each element of the installation, in addition to the compressor, directing the R-141b freon in a counterflow direction. In this case, it is rational to use flexible transparent hoses in order to ensure the cleanliness of the washing liquid, and therefore the cleanliness of the equipment oeing washed. But the transparency of the sleeves may deteriorate over time.

  • Refrigerants
  • refrigerator gas
  • Refrigerant gas
  • helium

Product characteristics

SKU
TH588IRL718846
MF
CH3CCI2F
EINECS No
4438719
Grade Standard
Industrial Grade
Purity
>99.9%
Moisture PPm
<50
Boiling Point C
-26.1
Molecular Weight
102.03
Critical Temperature C
101.1

Domain icon Manufacturer/ Producer

0000 Samut Prakan - Thailand

Contact