Rec15_AI1_5p Automatic Circuit Recloser

Description

Thousands of nodding donkey oil pumps were energized through an extensive and highly meshed overhead electrical network. Automated protection was performed only by the feeder CB at the substation. None of the line sectioning breakers were automated, so every single failure on the network required human intervention and led to significant outages. Solution Tavrida Electric installed and commissioned six Rec15 with Rezip* functionality on a single line in just one day. The following project outcomes were achieved Direct savings (outage time reduction → revenue loss reduction) Indirect savings (operation, maintenance, and repair cost reduction) Improvement of power supply quality and reliability Drastically improved network visibility and operator awareness *Rezip is an advanced Fault Detection, Isolation and Restoration (FDIR) algorithm

  • Electric transformers, converters and rectifiers
  • Circuit Recloser
  • Automatic Circuit

Product characteristics

Rated voltage
15.5 kV
Rated lightning impulse withstand voltage
110 kV
Rated continuous current
630 A
Rated breaking current
16 kA
Rated short time withstand current
16 kA, 4 s
Mechanical resource
30,000 CO
Rated operating sequence
O-0.1s-CO-2s-CO-2s-CO
Switching module weight
68 kg
Control cubicle weight
41 kg

Domain icon Manufacturer/ Producer

88069 Tettnang - Germany